Academic Research to Support Facility Guidelines Institute & ANSI/ASHRAE/ASHE Standard 170-2013

 

Academic Research to Support Facility Guidelines (cover)
by Roger Lautz, Dr. Fred Betz, Dr. Ehsan Mousavi

The purpose of this study was to conduct a literature review of ANSI/ASHE/ASHRAE Standard 170 Ventilation of Health Care Facilities to determine whether the 886 requirements defined in the Standard (Part 4 of the FGI Guidelines) are supported by engineering and/or scientific evidence. The authors and the Project Monitoring Subcommittee (PMS) assigned the requirements to one of three categories: rational inclusion, clinical inclusion and evidence-based inclusion.

Those requirements categorized for evidence-based inclusion were aligned with related citations. The authors provided opinions on whether the available evidence suggests that the requirement is a basic necessity or an enhanced requirement, requires a change to the Standard, is procedural or requires further investigation.

Overall, 209 requirements (23.6%) were determined to be a basic necessity as supported by rational inclusion, clinical requirements or evidence and six requirements (0.7%) were considered to be enhanced practices. Twelve requirements (1.4%) were determined to be procedural and not subject to evidence. Evidence was found to support a change to the standard for eight requirements (0.9%). The remaining 651 requirements (73.5%) are recommended for further study.

 

 Access PDF Members can download a PDF of the entire monograph
Order print version Catalog number: 055399
Member: $25.00, Nonmember: $35.00

 

 

Related Resources

Compliance Tools
The pre-disaster self-assessment consists of an assessment of critical infrastructure and an estimate of evacuation time.
On-Demand Educational Webinars
Kathleen Morlang, Kara Brooks, Peter Dahl, Scott Tripp. This webinar is a panel discussion on high-performance building design evaluating design…
On-Demand Educational Webinars
Learn how ASHE and its partners are conducting research on the impact of emerging electrical loads on health care facilities.